350 HP Mobile Boiler Room
Burnham Commercial DP-35-50-PF
The 350 HP Mobile Boiler Room by Burnham Commercial, a robust solution for your steam needs, all enclosed within a 48-foot trailer. At its core is the DP-350 Burnham Commercial Low NOx steam boiler, offering the flexibility of natural gas or No. 2 fuel oil, producing a remarkable 12,075 lbs. of steam per hour at 250 psi and 212°F. It’s designed for eco-friendliness, ensuring NOx emissions on Natural Gas stay as low as 30ppm at 3% O2, making it a clean and compliant choice. This comprehensive package includes a fully modulating high turndown Power Flame burner, a Deaerator system by Bryan Steam, primary feedwater pumps by Grundfos, chemical feed system, makeup water softener, blowdown separator, and more, making it a complete turnkey solution for your steam requirements. With insulated steam and feedwater piping and the right connection sizes, it’s ready for efficient integration, and its fuel consumption and power requirements are straightforward, ensuring a hassle-free experience.
350 HP Mobile Boiler Room
One (1) 350 horsepower mobile boiler room complete with one DP-350 Burnham Commercial Low NOx steam boiler, combination natural gas or No. 2 fuel oil fired, design pressure 250 psi, capable of producing 12,075 lbs. of steam per hour from and at 212 deg F. NOx emissions on Natural Gas will be 30ppm at 3% O2 from 25% to 100% MCR.
The boiler comes complete with gas train, oil train, No. 2 fuel oil pump, air compressor, second low water cut-off, pressure controls, flame safeguard control, relief valves, feedwater valves, blowdown valves, a fully modulating high turndown Power Flame burner.
This Rental System Also Includes:
- One (1) Deaerator system – Bryan Steam
- Two (2) Primary feedwater pumps – Grundfos with VFD Control’s
- One (1) Chemical feed system with pump, day tank, mixer, makeup meter and controls
- Twin canister makeup water softener with brine tank and controls
- One (1) surface blowdown controller with sensor and motorized ball valve
- One Atomization air compressor
- One Blowdown Flash tank/separator
- Electrical switch gear
- One (1) propane hose and regulator for pilot connection, if oil fired
- One (1) main steam stop valve
- One (1) operator’s manual
- One Stub Stack
The unit is pre-piped and totally enclosed in a 48’’ trailer. Steam and Feedwater piping is insulated.
Connection Sizes:
- Main steam outlet – 6”, 300# flanged, OS&Y Valve and DFT included
- Natural gas connection – 2 1/2″, 150# flanged
- Maximum inlet pressure to gas regulator – 10 PSIG
- Oil is pre-piped
- Feedwater – 1 1/2″ MPT
- Blowdown Seperator Drain – 5″ Must be full flow
Fuel Requirements:
- Natural gas – 14,670 SCFH
- No. 2 fuel oil – 105 GPH
Voltage and Amperage Requirements:
- 480 volts 150 amp service, 3 phase
Interested in Learning More About Our Rental Boiler Systems?